American Society of Sanitary Engineering
 
Product Standards Descriptions
 

If you know which Standard you are looking for, click on the link below.

ASSE Standard # 1001- 2008
Performance Requirements for Atmospheric Type Vacuum Breakers

This standard applies to atmospheric type vacuum breakers that are single pipe-applied (does not apply to tank ball cocks or similar devices that depend on float operated valves to control flow). The purpose of these devices is to provide protection of the potable water supply against pollutants or contaminants that enter the system due to backsiphonage through the outlet. Under backsiphonage conditions, a small amount of water is permitted to exit through the air ports.

The device shall: 1) Be installed downstream of the last control valve; 2) Not be subjected to backpressure; 3) Not be subjected to more than 12 hours of continuous water pressure; and 4) Be installed with its critical level (CL) not less than 6.0 inches (152.4 mm) above the flood level rim of the fixture or appliances served; or deck mounted/equipment mounted atmospheric vacuum breakers shall be installed in accordance with the manufacturer's instructions, with its critical level (CL) not less than 1.0 inch (25.4 mm) above the flood level rim of the fixture or appliance served. Order here

ASSE Standard #1002-2008
Performance Requirements for Anti-Siphon Fill Valves for Water Closet Tanks

Provides dimensional and minimum performance requirements for anti-siphon fill valves for water closet tanks, including protection of the potable water supply against back siphonage of water from the water closet tank. Order here

ASSE Standard #1003-2001
Performance Requirements for Water Pressure Reducing Valves

ANSI Approved - 2001

Devices covered by this standard are self-contained, direct acting, single diaphragm types. Devices shall be permitted to have an integral strainer, separate strainer connected to the valve inlet, or be without strainer. Devices shall be permitted to be with or without an integral bypass relief valve. The purpose of this device is to reduce static and flowing pressures in water distribution systems.
Order here

ASSE Standard #1004-2008
Performance Requirements for Backflow Prevention Requirements for Commercial Dishwashing Machines

Covers the requirements for the protection of the potable water supply from pollution as a part of and within a commercial dishwashing machine and the means of discharging waste.
Order here

ASSE Standard #1006-1986
Performance Requirements for Residential Use Dishwashers

Applies to residential use (household) type dishwashers, both front loading and top loading, requiring connection to the potable water supply and discharging into the plumbing drainage system.
Order here

ASSE Standard #1007-1986
Performance Requirements for Home Laundry Equipment

Applies to household type automatic and semiautomatic clothes washers, combination washer-dryers, and dryers including those household types that are coin-operated, requiring connection to the potable water supply and discharging into the building plumbing drainage system.
Order here

ASSE Standard #1008-2006
Performance Requirements for Plumbing Aspects of Residential Food Waste Disposer U
nits
ANSI Approved - 2006

Applies to the plumbing aspects of residential food waste disposers intended for installation in the residential kitchen sink outlet, which when supplied with water from the sink supply faucet discharge into the sanitary drainage system.
Order here

ASSE Standard #1009-1990
Performance Requirements for Commercial Food Waste Grinder Units

Applies to food waste grinders designed and intended for use in food establishments, supplied with water and which discharges waste into a plumbing drainage system. Order here

ASSE Standard #1010-2004
Performance Requirements for Water Hammer Arresters

ANSI Approved - 2004

Applies only to those devices classified as water hammer arresters having a permanently sealed cushion of water or gas isolated from the waterway, and designed to provide continuous protection, without maintenance, against detrimental surge pressures within the water distribution system. Water hammer arresters are installed on water distribution system piping to prevent over pressures within water distribution systems, thereby prolonging the service life of valves, piping, fittings, trim, equipment, appliances, appurtenances, and other devices which are part of the distribution system; and to eliminate noise.
Order here

ASSE Standard #1011-2004
Performance Requirements for Hose Connection Vacuum Breakers

ANSI Approved - 2004

Applies only to those devices classified as Vacuum Breakers, Hose Connection Type, which are designed to be installed on the discharge side of the hose bibb, hydrant or faucet which is fitted with hose threads. The design embraces a check valve member force loaded, or biased, to a closed position, and an atmospheric vent valve, force loaded, or biased, to an open position when the device is not under pressure. This device shall not be subjected to continuous pressure. Continuous pressure shall mean twelve (12) hours use in a twenty-four (24) hour period. Mechanical means used to defeat the vacuum breaker shall not be used. This device shall only be used on systems where the only source of low head back pressure comes from an elevated hose equal to or less than three (3.0) meters (10 feet) in height.
Order here

ASSE Standard #1012-2002
Performance Requirements for Backflow Preventer with Intermediate Atmospheric Vent

ANSI Approved - 2002

The devices covered by this standard are those which have functional capabilities for preventing both backsiphonage and back pressure backflow in the potable water supply lines, and which can operate under continuous or intermittent pressure conditions. These devices have two independently operating check valves separated by an intermediate chamber with a means for automatically venting it to the atmosphere. The check valves are force loaded to a normally closed position and the venting means is force loaded to a normally open position.
Order here

ASSE Standard #1013-2005
Performance Requirements for Reduced Pressure Principle Backflow Preventers and Reduced Pressure Fire Protection Principle Backflow Preventers

ANSI Approved - 2005
Applies only to two types of backflow prevention assemblies identified as (RP) “Reduced Pressure Principle Backflow Preventers” and (RPF) “Reduced Pressure Principle Fire Protection Backflow Preventers.” These assemblies consist of two (2) independently-acting check valves, internally force loaded to a normally closed position, and separated by an intermediate chamber (or zone) in which there is an hydraulically operated relief means for venting to atmosphere, internally force loaded to a normally open position. These assemblies are designed to operate under continuous pressure conditions. The assembly shall include two (2) tightly closing shut-off valves, and contain properly located test cocks. This standard also applies to Manifold Reduced Pressure Principle Backflow Assemblies. They consist of two or more complete Reduced Pressure Principle Backflow Preventers in parallel. The assemblies do not need to be of the same pipe size. The manifold size shall be identified by the single inlet and outlet of the manifold reduced pressure principal backflow assembly. It shall consist of shut-off valves on the inlet and outlet of each of the assemblies in the manifold and the shut-off valves shall be line sized to each backflow assembly in the manifold. Order here

ASSE Standard #1014-2005
Performance Requirements for Backflow Prevention Devices for Hand-Held Showers

ANSI Approved - 2005
Provides performance requirements for backflow prevention device(s) for hand-held showers in the interest of health and safety. These devices provide backflow protection against backsiphonage and backpressure in hand-held showers. These are separate devices or are integral with wall-mounted or deck-mounted tub fillers, flexible hoses, or components that are attached to shower arms.
 Order here

ASSE Standard #1015-2005
Performance Requirements for Double Check Backflow Prevention Assemblies and Double Check Fire Protection Backflow Prevention Assemblies

ANSI Approved - 2005

Applies to two types of backflow prevention assemblies identified as a (Double Check Backflow Prevention Assembly (DC) and a Double Check Fire Protection Backflow Prevention Assembly (DCF). These assemblies consist of two (2) independently acting check valves, internally force loaded to a normally closed position, two (2) tightly closing shut-off (isolation) valves, and properly located test cocks. These assemblies are designed and constructed to operate under intermittent or continuous pressure conditions. This standard also applies to Manifold Double Check Backflow Prevention Assemblies. These consist of two or more complete Double Check Backflow Prevention Assemblies in parallel.
Order here

ASSE Standard #1016-2005
Performance Requirements for Automatic Compensating Valves for Individual
Showers and Tub/Shower Combinations

ANSI Approved - 2005
Automatic Compensating Valves for Individual Showers and Tub/Shower Combinations are intended to control the water temperature to wall mounted shower heads either in individual shower or tub/shower combination fixtures in order to reduce the risk of scalding and thermal shock. These devices are intended to be installed at the point-of-use, where the bather or bather’s attendant has access to flow and final temperature control mechanisms, and where no further mixing occurs downstream of the device. The three (3) types of individual control valves covered by this standard are: 1. Pressure balancing valves (Type P) have a mechanism that senses incoming hot and cold water pressures and compensates for fluctuations in either to stabilize outlet temperature. 2. Thermostatic valves (Type T) have a mechanism that senses outlet temperature and compensates for fluctuations in either incoming hot and cold water temperature and/or pressure to stabilize outlet temperature. 3. Combination thermostatic/pressure balancing valves (Type T/P) sense outlet temperature and incoming hot and cold water pressures and compensates for fluctuations in incoming hot and cold water temperatures and/or pressures to stabilize the outlet temperature. These devices are intended to be the final temperature control.
Order here

ASSE Standard #1017-2003
Performance Requirements for Temperature Actuated Mixing Valves for Hot Water Distribution Systems

Temperature Actuated Mixing Valves for Hot Water Distribution Systems are used for controlling in-line water temperatures in domestic potable hot water systems and shall be installed at the hot water source. They are not intended for end use application. Temperature Actuated Mixing Valves for Hot Water Distribution Systems shall consist of a hot water inlet connection, a cold water inlet connection and a mixed water outlet connection plus a temperature sensing and controlling element and a means for adjusting the outlet water temperature. Order here

ASSE Standard #1018-2001
Performance Requirements for Trap Seal Primer Valves - Potable Water Supplied

ANSI Approved - 2002
Devices covered by this standard are designed primarily to supply water to drain traps which have infrequent use and in which water evaporation would allow sewer gas to enter the premises. This type of device is located in the domestic water distribution system and is designed to supply potable water to a drain trap to maintain the water seal. A means for the prevention of backsiphonage shall be incorporated as part of the device.
Order here

ASSE Standard #1019-2004
Performance Requirements for Vacuum Breaker Wall Hydrants, Freeze Resistant, Automatic Draining Type

ANSI Approved - 2004
The purpose of these devices is to supply potable water without danger of damage to the device due to freezing; and to provide protection of the potable water supply from contamination due to back siphonage or back pressure less than or equal to 3 meters (10 feet) of head pressure. This standard covers design and performance requirements for water supply system wall hydrant devices. These devices shall have a permanent means including air inlet valve(s) to prevent backflow from a potential health hazard due to back siphonage, and back pressure less than 3 meters (10 feet) of head pressure. The device shall only be used on systems where the only source of back pressure comes from an elevated hose equal to or less than 3 meters (10 feet) in height and from full rated supply pressure. The devices shall be classified as follows: (a) Type A: These hydrants automatically drain the water when the water supply is shut off and the hose removed to prevent damage from freezing; (b) Type B: These hydrants automatically drain the water with a hose removed or attached, end nozzle closed, and the hydrant valve closed; and (c) Type C: Same as Type A. Backflow prevention is achieved by alternate principle of holding pressure versus relieving pressure.
Order here

ASSE Standard #1020-2004
Performance Requirements for Pressure Vacuum Breaker Assembly

ANSI Approved - 2004

Pressure vacuum breaker assemblies are for installation in water supply lines to prevent the entrance of non-potable material into the potable water supply by backsiphonage only. It is not for use in any system where backpressure can be applied to the assembly. When a supply pressure is between 7 to 14 kPa (1 to 2 p.s.i.), the air inlet valve is open and the assembly will continuously dis­charge. Due to this probability of water discharge from the at­mospheric air inlet valve, the assembly shall only be installed where water discharge does not cause damage.
Order here

ASSE Standard #1021-2001
Performance Requirements for Drain Air Gaps for Domestic Dishwasher Applications

ANSI Approval Pending

Products covered by the standard are devices for installation in the drain line of residential dishwashers. The purpose of this device is to prevent the backflow of contaminated liquid and entrained material into the dishwasher.
Order here

ASSE Standard #1022-2003
Performance Requirements for Backflow Preventer for Beverage Dispensing Equipment

ANSI Approved - 2003

Covers a backflow prevention device designed to protect the potable water supply serving beverage dispensing equipment. These devices are intended for use under continuous or intermittent pressure conditions. They shall consist of two independently acting check valves biased to a normally closed position. An atmospheric port shall be located between the check valves and shall be biased to a normally open position. The port shall vent liquids, gases, or both, under backflow conditions. Order here

ASSE Standard #1023-1979
Performance Requirements for Hot Water Dispensers Household Storage Type - Electrical

The hot water dispensers covered by this standard are those which are designed for household use and which are installed at the sink and supplied with water from the kitchen sink water supply. They are storage types, continuously vented to atmosphere and heated electrically. Order here

ASSE Standard #1024-2004
Performance Requirements for Dual Check Backflow Preventers

ANSI Approved - 2004
Applies only to the type of backflow preventer identified as a dual check backflow preventer.  This device consists of two (2) independently acting check valves, internally force loaded to a normally closed position, designed and constructed to operate under intermittent or continuous pressure conditions. The purpose of the dual check backflow preventer is to keep polluted water from flowing back into the potable water system, when pressure is temporarily higher in the polluted part of the system than in the potable water piping. The devices covered by this standard are intended to protect the potable water supply from low hazard pollution at residential service lines and individual outlets. These devices are intended for cold water service under continuous or intermittent pressure conditions. Usage with hot water is limited to the temperature specified by the manufacturer.
Order here

ASSE Standard #1032-2004
Performance Requirements for Dual Check Valve Type Backflow Preventers For Carbonated Beverage Dispensers - Post Mix Type

The devices covered by this standard are those with functional capabilities for preventing back pressure backflow in water supply lines, and which can operate under continuous or intermittent pressure conditions. These devices consist of two independently acting primary check valves, internally force loaded to a normally closed position, in a common casing or valve body. Devices may have a supplementary check valve downstream of the primary downstream check valve. Where it is incorporated in the design, it shall be held open by suitable means or removed for all performance tests where noted.
Order here

ASSE Standard #1035-2008
Performance Requirements for Laboratory Faucet Backflow Preventers

Laboratory Faucet Backflow Preventers are designed to protect the potable water supply from pollutants or contaminants which enter the system by backflow due to back siphonage or back pressure. This standard applies only to those devices classified as backflow preventers that are designed for installation on laboratory faucets on the discharge side of the last shut-off valve. These devices are not for use under constant pressure conditions. These devices consist of two independently acting check valves, force loaded or biased to a normally closed position, and between the check valves a means for automatically venting to atmosphere, force loaded or biased to normally open position. Order here

ASSE Standard #1037-1990
Performance Requirements for Pressurized Flushing Devices (Flushometers) for Plumbing Fixtures

Establishes basic performance requirements for pressurized flushing devices, for the safe and sanitary operation of plumbing fixtures.
Order here

ASSE Standard #1043-1992
Performance Requirements for Cast Iron Sovent Sanitary Drainage Systems

Establishes functional performance requirements for cast iron sovent drainage fittings, aerators and deaerators, and installation guidelines for the system. A cast iron sovent system is a single-stack drainage, waste and vent system that uses special fittings (aerators and deaerators) to maintain the differential pressures within the system near atmosphere, thereby protecting the trap seals of the connected fixtures. Order here

ASSE Standard #1044-2001
Performance Requirements for Trap Seal Primer Devices - Drainage Types and Electronic Design Types

ANSI Approved - 2002

Devices covered by this performance standard are designed primarily to supply water to floor drain traps which have infrequent use and in which water evaporation would allow sewer gas to enter the premises. The type of device covered by this standard is designed to supply water to a drain trap to provide and maintain its water seal using a supply from a fixture drainline, ballcock, or flushometer valve tailpiece or an electronic primer device. The rate of water flow to the trap shall be permitted to be fixed or
adjustable. The devices are of four (4) types: (a) Those which are installed on waste line tail pieces from fixtures, such as lavatories, sinks and similar fixtures where grease is not normally generated; (b) Those which are used in conjunction with ballcock assemblies; (c) Those which receive flow from flushometer valves; and (d) Those electronics devices which discharge water automatically and which are upstream of the air gap or vacuum breaker. Order here

ASSE Standard #1047-2005
Performance Requirements for Reduced Pressure Detector Fire Protection Backflow Prevention Assemblies

ANSI Approved - 2005

Applies to the type of assembly identified as Reduced Pressure Detector Fire Protection Backflow Prevention Assemblies (RPDF). This assembly consists of two (2) independently-acting check valves, internally force loaded to a normally closed position, and separated by an intermediate chamber (or zone) in which there is a hydraulically operated relief means for venting to atmosphere, internally force loaded to a normally open position. These assemblies are designed to operate under continuous pressure conditions. This standard also applies to Manifold Reduced Pressure Fire Protection Backflow Prevention Assemblies. They consist of two or more complete RPDF assemblies in parallel. The assemblies do not need to be of the same pipe size.
Order here

ASSE Standard #1048-2005
Performance Requirements for Double Check Detector Fire Protection Backflow Prevention Assemblies

ANSI Approved - 2005
Applies to the type of backflow prevention assembly identified as Double Check Detector Fire Protection (DCDF). These assemblies consist of two (2) independently-acting check valves, internally force loaded to a normally closed position. These assemblies are designed to operate under continuous pressure conditions. This standard also applies to Manifold DCDF assemblies. They consist of two (2) or more complete DCDF assemblies in parallel. The assemblies do not need to be of the same pipe size. The manifold size shall be identified by the single inlet and outlet of the manifold DCDF assembly. It shall consist of shut-off valves on the inlet and outlet of each of the assemblies in the manifold and the shut-off valves shall be line sized to each DCDF assembly in the manifold.
Order here

ASSE Standard #1050-2002
Performance Requirements for Stack Air Admittance Valves for Sanitary Drainage Systems

ANSI Approval Pending
Stack Air Admittance Valves for Sanitary Drainage Systems are used as vent terminals for stacks in plumbing drainage systems. These devices shall not be used to relieve back pressure, but only to allow air to enter the system. When these devices are installed in a building, there shall be at least one (1) open vent terminal which extends to atmosphere outside of the building serving the building drain on which these devices are installed. These devices are designed to be installed on stacks where branches on multiple floors are connected. These devices consist of a one-way valve designed to allow air to enter the plumbing drainage system when a pressure less than atmospheric develops. The device closes and seals by gravity under zero (0) differential pressure (static or no flow condition) and under positive pressure. These devices prevent sewer gases from entering a building. The device consists of a hooded or shielded body which contains a movable guided diaphragm which seats and seals air flow when closed and allows air to enter when open.
Order here

ASSE Standard #1051-2002
Performance Requirements for Individual and Branch Type Air Admittance Valves for Sanitary Drainage Systems

ANSI Approval Pending

Individual and Branch Type Air Admittance Valves for Sanitary Drainage Systems (AAV’s) are used as vent terminals for individual and branch fixtures in plumbing drainage systems. These devices shall not be used to relieve back pressure, but only to allow air to enter the system. When the devices are installed in a building, there shall be at least one (1) open vent terminal which extends to atmosphere outside of the building serving the same building drain on which these devices are installed. These devices are designed to be used for individual fixtures or for a branch serving multiple fixtures. These devices consist of a one-way valve designed to allow air to enter the plumbing drainage system when a pressure less than atmospheric develops. The device closes and seals by gravity under positive pressure. These devices prevent sewer gases from entering the building. The device consists of a hooded or shielded body which contains a movable guided diaphragm which seats and seals air flow when closed and allows air to enter when open. Order here

ASSE Standard #1052-2004
Performance Requirements for Hose Connection Backflow Preventers

ANSI Approved - 2004
Establishes physical requirements, basic performance requirements and test procedures for hose connection backflow preventers. This device is designed to be installed on the discharge side of a hose threaded outlet on a potable water system. This two-check device protects against backflow, due to backsiphonage and low-head backpressure, under the high hazard conditions present at a hose threaded outlet. This device shall only be used on systems where sources of backpressure are not introduced. This device shall only be used on systems where the low-head backpressure does not exceed that generated by an elevated hose equal to or less than 3 m (10 ft.) in height. This device shall not be subjected to more than twelve (12) hours of continuous water pressure. A hose connection backflow preventer shall consist of two independent checks, force loaded or biased to a closed position, with an atmospheric vent located between the two check valves, which is force loaded or biased to an open position, and a means for attaching a hose.
Order here

ASSE Standard #1053-2004
Performance Requirements for Dual Check Backflow Preventer Wall Hydrants - Freeze Resistant Type

Establishes design and performance requirements and test procedures for Dual Check Backflow Preventer Wall Hydrants - Freeze Resistant. The purpose of these devices is to provide protection of the potable water supply from contamination due to backsiphonage or backpressure without damage to the device due to freezing, and is field testable to verify protection under the high hazard conditions present at a hose threaded outlet. This device shall only be used on systems where the low-head backpressure does not exceed that generated by an elevated hose equal to or less than 10.0 feet (3.0 m) in height, and are not subjected to continuous water pressure.
Order here

ASSE Standard #1055-1997
Performance Requirements for Chemical Dispensing Systems

Chemical dispensing systems provide a means of mixing potable water with chemicals to provide the user with a chemical solution which is ready for use. The amount of dilution shall be fixed or adjustable. This standard applies to those devices classified as chemical dispensing systems having self- contained means of backflow protection. The devices shall be classified as follows: (a) Type A: These devices have the chemical(s) pressurized above atmospheric pressure; and (b) Type B: These devices do not pressurize the chemical(s) above atmospheric pressure with the only source of back pressure coming form an elevated hose. Order here

ASSE Standard #1056-2001
Performance Requirements for Spill Resistant Vacuum Breaker

ANSI Approved - 2002
Spill Resistant Vacuum Breakers are installed in the potable water supply lines to prevent the backflow or nonpotable material into the potable water supply caused by backsiphonage only. They are not for use in any system where back pressure is applied to the device. When the system is pressurized, the vent closes to prevent a flow through the upstream check valve, and to eliminate vent spillage. This standard applies only to those devices classified as Spill Resistant Vacuum Breakers - SVB. These devices are designed for installation in those portions of the domestic potable water systems that are normally under continuous pressure conditions. The device includes one (1) check valve force-loaded closed and an air inlet vent valve force loaded open to atmosphere, positioned downstream of the check valve, and located between and including two (2) tightly closing shut-off valves and two (2) test cocks. Order here

ASSE Standard #1057-2001
Performance Requirements for Freeze Resistant Sanitary Yard Hydrant with Backflow Protection

ANSI Approval Pending

The purpose of freeze resistant sanitary yard hydrants is to supply potable water without danger of damage to the hydrant due to freezing, to provide protection of the potable water supply from contamination due to ground water, and to prevent backflow in accordance with the backflow prevention device selected. These devices shall only be used on systems where the low-head backpressure does not exceed that generated by an elevated hose equal to or less than 3 m (10 ft. ) in height. This device shall not be subjected to continuous pressure.
Order here

ASSE Standard #1060-2006
Performance Requirements for Outdoor Enclosures for
Fluid Conveying Components

ANSI Approved - 2006

Focuses on devices that provide a range of protection for fluid conveying components which are mounted outside & above ground so that they may avoid damage from freezing, vandalism & tampering. Fluid conveying components include backflow prevention assemblies & devices, water meters, control valves, pressure reducing valves, air release valves, pumps & other components installed outdoors & above ground that require protection from freezing or require system security protection.
Order here

ASSE Standard #1061-2006
Performance Requirements for Removable & Non-Removable Push-Fit Fittings

ANSI Approved - 2006
Applies to push-fit fittings than can be used with one or more of the following materials:
1) PEX tubing complying with ASTM F 876 or ASTM F 877;
2) Type K, L and M copper tubing complying with ASTM B 88; and
3) CPVC tubing complying with ASTM D 2846.

Push-fit fittings may be designed to be used with one or more types of tubing that conform to the dimensions as specified in their respective standard. This standard serves to supplement ASTM F 877, ASTM D 2846 & ASTM B88 in describing a test method for a specific type of push-fit fitting system to be used with PEX, Copper &/or CPVC tubing. This standard covers minimum requirements for materials of construction & prescribes minimum performance requirements for fitting joints, marking & identification.
Order here

ASSE Standard #1062-2006
Performance Requirements for Temperature Actuated, Flow Reduction (TAFR) Valves for Individual Fixture Fittings

ANSI Approved - 2006
Applies to Temperature Actuated, Flow Reduction (TAFR) Valves for Individual Supply Fittings which react to high temperature water. These valves are intended for use in-line with or are integrated into individual plumbing supply fittings such as shower heads, bath and utility faucets and sink and lavatory faucets. These devices shall automatically reduce flow within five (5) seconds to 0.25 GPM (0.95 L/m) or less at 80 psi (551.6 kPa) in response to outlet temperatures greater than a preset actuation temperature not to exceed 120 °F (48.9 °C) so as to limit exposure to high temperature water discharged from an individual supply fitting.
Order here

ASSE Standard #1063-2008
Performance Requirements for Air Valve & Vent Intake Preventers

The purpose of Air Valve and Vent Inflow Preventer Assemblies is to allow the release and admission of high volumes of air through air valves and air vents in water distribution systems but prevent the entry of contaminated water when the air valve outlet becomes submerged from flooding or is the target of malicious tampering.

This assembly shall consist of a primary and a secondary chamber. Each chamber shall contain an independent float-operated closure member. The primary chamber is the lower chamber. The secondary or upper chamber is redundant and will close in the event the primary chamber fails to close. Order here

ASSE Standard #1064-2006
Performance Requirements for Backflow Prevention Assembly Field Test Kits

ANSI Approved - 2006
Portable backflow prevention assembly field test kits (BFTK) shall be used in testing the performance of backflow prevention assemblies. This standard covers the performance requirements, and accuracy of a BFTK. This standard is confined to analog dial type and digital instrumentation. Duplex gauges are not a part of this standard. They shall be designed to indicate the operation of a backflow prevention assembly to pre-established testing procedures. The backflow field test kit shall include all gauges, hoses, valves and fittings as required for testing purposes.
Order here

ASSE Standard #1066-1997
Performance Requirements for Individual Pressure Balancing In-Line Valves for Individual Fixture Fittings

Applies to automatic pressure balancing in-line valves which are used to equalize incoming hot and cold water line pressures for the purpose of minimizing mixed water temperature variations due to pressure fluctuations when used in conjunction with a mixing valve or two handle valve set. They are not designed to limit the maximum outlet temperature at the point-of-use. These devices are intended for use in individual plumbing fixtures fittings such as shower heads, bath utility faucets, and sink and lavatory faucets.
Order here

ASSE Standard #1069-2005
Performance Requirements for Automatic Temperature Control Mixing Valves

ANSI Approved - 2005

These devices shall be designed to supply only tempered water to the end user, and automatically compensate for pressure and/or temperature variations in water distribution systems. These devices shall have the capability to significantly reduce the outlet flow in the event of a cold water distribution system failure. The device shall be equipped with an adjustable means to limit the setting of the device towards the hot position. The device is designed to be the final temperature control.
Order here

ASSE Standard #1070-2004
Performance Requirements for Water Temperature Limiting Devices

ANSI Approved - 2004
Water Temperature Limiting Devices shall control and limit the water temperature to fittings for fixtures such as sinks, lavatories or bathtubs and are intended to reduce the risk of scalding. These devices are intended to supply tempered water to plumbing fixture fittings, or be integral with plumbing fixture fittings supplying tempered water. The device shall be equipped with an adjustable and lockable means to limit the setting of the device towards the hot position. Where the device is integral to the fixture fitting, it shall comply with the requirements of ASME A112.18.1.
Order here

ASSE Standard #1071-2008
Performance Requirements for Temperature Actuated Mixing Valves for Plumbed Emergency Equipment

Water mixing (also defined as tempering or blending) valves are used extensively in applications for emergency shower/eye and face wash systems to mix hot and cold water to provide "tepid" water. The term "tepid" has not been specifically defined, but is generally understood to mean "lukewarm" or "moderately warm". Valves designed to meet this standard are intended to be used as a component that can provide tepid water for emergency eye wash and shower equipment that comply with the requirements of ANSI Standard Z358.1.
Order here

ASSE Standard #1072-2007
Performance Requirements for Barrier Type Floor Drain Trap Seal Protection Devices

This new ASSE Standard #1072 introduces an alternative method of protecting floor drain water trap seals- Barrier-Type Floor Drain Trap Seal Devices. Because this barrier method does not automatically and periodically provide water to replenish the trap seal, it must provide a barrier on the inlet side of the trap seal that will minimize its evaporation caused by the ambient air on the building side of the trap. This barrier must also provide adequate drainage capabilities required for the floor drain’s intended use as determined by its design, size, and installation location.

While developing the performance requirements and tests for these devices, certain adverse conditions were taken into consideration. These are the introduction of fouling substances such as dirt/sand, floor wax or grease directly into the device. In addition drainage requirements to accommodate infrequent, and unusually sizeable, water flows caused by water line breaks, fixture overflows or backflow preventer discharges are provided. Tests are included to confirm that devices submitted for approval provide the performance requirements listed above- among others. Order here

ASSE Standard #1079-2005
Performance Requirements for Dielectric Pipe Unions

Dielectric pipe unions are designed to prevent stray current in piping systems. These stray currents can come from dissimilar piping materials or improper grounding of electrical equipment. This standard provides guidance in the construction of pipe unions that incorporate electrical insulating properties to reduce the accelerated corrosion that can result from galvanic and stray currents.
Order here

ASSE SERIES 5000-2004
Professional Qualifications Standard for Backflow Prevention Assemblies Testers, Repairers and Surveyors
Appl
ies to any field inspection performance requirement used to appraise the performance of:
• Reduced Pressure Principle Backflow Preventers and Reduced Pressure Fire Protection Principle Backflow Preventers (ASSE 1013)
• Double Check Backflow Prevention Assemblies and Double Check Fire Protection Backflow Prevention Assemblies (ASSE 1015)
• Pressure Vacuum Breaker Assembly (ASSE 1020)
• Reduced Pressure Detector Fire Protection Backflow Prevention Assembly (ASSE 1047)
• Double Check Detector Fire Protection Backflow Prevention Assemblies (ASSE 1048)
• Hose Connection Backflow Preventer (ASSE 1052)
• Spill Resistant Vacuum Breaker (ASSE 1056)

Also applies to any individual who is certified in accordance with this standard and who will:
• Test all types of backflow preventers
• Perform a cross-connection control survey inspection
• Repair all approved ba
ckflow preventers. Order here

SERIES 6000-2006
Professional Qualifications Standard for Medical Gas Systems Personnel

ANSI Approved -
2006

6005 - Medical Gas Systems Specialist
Provides general knowledge of medical gas and vacuum systems for the purpose of providing continuing education. Eligible individuals include any person with an interest in medical gas and vacuum systems and equipment.

6010 - Medical Gas Systems Installers
Applies to any individual who installs medical gas and vacuum systems. Installers include anyone who works on or installs piping or components, including brazers.

6015 - Bulk Medical Gas Systems Installers
Applies to any individual who installs bulk systems for medical gas at health care facilities. Installers include anyone who works on or installs bulk systems or bulk system components, including brazers on bulk supply systems.

6020 - Medical Gas Systems Inspectors
Applies to any individual who inspects the installation of medical gas and vacuum distribution pipeline systems.

6030 - Medical Gas Systems Verifiers
Applies to any individual who tests and verifies the operation of medical gas and vacuum systems.

6040 - Medical Gas Systems Maintenance Personnel
Applies to any individual who maintains medical gas and vacuum systems.

6050 - Medical Gas Systems Instructors
Applies to any individual who trains or teaches installers, inspectors, verifiers and healthcare facility maintenance personnel regarding medical gas and vacuum distribution systems.

6055 - Bulk Medical Gas Systems Instructors
Applies to any individual who trains or teaches bulk system installers.
Order here

ASSE Home  |  Search the ASSE Website  |  Contact the WebMastress  |  Sitemap